Heat Exchanger

Calculates gas-side pressure drop, outlet temperature, and heat duty using external temperature and conductance, or specified heat flux.

Component Appearance and Location​

Expand Heat Exchange Treatment in the component library on the left and find "Heat Exchanger".

Created with Fabric.js 5.3.0

Ports and Connections​

Port KeyTypeDirectionInterface NameDisplay Conditions
0FLUIDinputfluid inletalways show
1FLUIDoutputFluid outletalways show

Connect in the main flow direction. Port 0 is upstream for forward flow; 1 for reverse flow. Bind measurements and commands with a measurement instrument or actuator.

Parameter List​

Equipment Specifications

NamekeyTypeDefault / OptionsDescription
Flow Coefficient Kv [m³/(h·bar⁰ᐧ⁵)]FullOpenKVreal5000Gas-side pressure-drop coefficient from equipment resistance data. Larger Kv gives less drop at equal flow/state.
Effective Heat Transfer Area [m²]HeatTransferAreareal10Effective area for heat transfer, sharing coefficient/flux area basis; use equipment data.

Control Mode

NamekeyTypeDefault / OptionsDescription
Heat Transfer ModeHeatExchangeModechoiceExternal Temperature and Overall Coefficient / Specified Heat FluxDetermine duty from external temperature/coefficient/area, or specified heat flux/area.
Control SourceControlModechoice0Plans/signals apply only in transients. Steady-state uses initial/static physical parameters, retaining saved source/wiring.

Heat Transfer Parameters

NamekeyTypeDefault / OptionsDescription
Overall Coefficient SourceHeatTransferCoefficientInputModechoiceFixed Value / Time CurveFixed or time-varying overall coefficient.
Overall Heat Transfer Coefficient [W/(m²·K)]HeatTransferCoefficientreal50Overall gas/external-medium coefficient on the effective area basis; zero means adiabatic.
Overall Heat Transfer Coefficient CurveCurveLibraryHeatTransferCoefficientNamechoice__UNSELECTED__Select an overall heat transfer coefficient curve whose area basis matches this component's heat transfer area.
External Fluid Temperature SourceExternalTemperatureInputModechoiceFixed Value / Time Curve / Temperature SignalFixed, curve, or temperature signal; signal mode needs external-temperature actuation adapter.
External Fluid Temperature [℃]ExternalTemperaturereal10External heating/cooling medium temperature sets thermal driving difference/direction.
External Fluid Temperature CurveCurveLibraryTemperatureNamechoice__UNSELECTED__Select an external fluid temperature curve. A steady-state run uses its value at the simulation start time.
Heat Flux SourceHeatFluxInputModechoiceFixed Value / Time Curve / Heat Flux SignalFixed, curve, or heat-flux signal. Signal mode needs heat-flux adapter; legacy heat-duty signals still use heat-duty adapters.
Heat Flux [W/m²]HeatFluxreal0Power per effective area, positive heating/negative cooling. Times area gives requested duty, limited by capacity; actual duty is zero without flow.
Heat Flux CurveCurveLibraryHeatFluxNamechoice__UNSELECTED__Select a heat flux curve. Positive values heat the gas and negative values remove heat. The solver calculates the heat load using this component's heat transfer area.
Thermal Conductance UA [W/K]UAreal500Overall coefficient × area.
External Fluid Temperature [℃]ColdSideTemperaturereal10Cooling/heating medium temperature.

Operating Constraints

NamekeyTypeDefault / OptionsDescription
Maximum Heating Duty [kW]MaximumHeatingDutyreal1000Equipment duty limit for specified heat flux/duty.
Maximum Cooling Duty [kW]MaximumCoolingDutyreal1000Equipment duty limit for specified heat flux/duty.

Transient Events

NamekeyTypeDefault / OptionsDescription
Event ChainEventstableConfigure one row at a timeExternal-temperature events with linear interpolation between rows.
Event Chain / TimeEvents.timedatetime2026-01-01 00:00:00Time
Event Chain / External Fluid Temperature [℃]Events.coldSideTemperaturereal10External cooling/heating temperature at this time.

Parameter Guidance​

Set Kv from gas-side pressure-drop data. Effective area must share the basis used for overall coefficient or heat flux.

ModeUseTransient input
External temperature and overall coefficientKnown external temperature and conductance; gas state and flow determine dutyU in W/(m²·K): fixed or time curve. External °C: also temperature signal.
Specified heat fluxKnown heating/cooling per unit areaW/m²: fixed, time curve, or signal. Heating/cooling limits: separate nonnegative kW values.

Steady-state calculations use the current panel values. Control signals apply during transients. Time curves are interpolated linearly at the end of each transient step and at the calculation start for the initial state.

Enter Curves​

Set the relevant input to Time Curve, then select its Curve Source. Configure curves for overall heat transfer coefficient, external temperature, and heat flux separately. The calculation uses the inputs for the selected heat transfer mode.

CurveLocal pointsDatabase sourceUnits
Overall heat transfer coefficientTime and overall heat transfer coefficientOverall heat transfer coefficient curveW/(m²·K)
External temperatureTime and external medium temperatureTemperature curve°C
Heat fluxTime and heat fluxHeat flux curveW/m², positive for heating and negative for cooling

Use Edit Local Curve to enter points on the component or Reference Curve Database to select a named curve of the same type. Time must increase strictly and cover the calculation interval. Heat flux times effective transfer area gives the requested heat duty. Area AA times coefficient UU gives thermal conductance UAUA. Choose a curve source.

Modeling Steps​

  1. Connect gas ports in main direction.
  2. Enter Kv.
  3. For non-isothermal mode, select thermal mode and area.
  4. In external-temperature mode, choose the sources for overall coefficient and external medium temperature. In specified-heat-flux mode, choose the heat flux source. For each time curve, enter local points or select a database curve.
  5. Bind actuators for signal inputs; set heating/cooling limits for specified flux.
  6. Add measurement instruments if needed.
  7. Check drop, heat direction, temperatures, and actual duty.

View Results​

  • Ports. Determine actual upstream by flow sign before comparing state.
  • Temperature/coefficient mode. Compare external temperature, coefficient, and actual duty.
  • Flux mode. Compare requested, adopted, and actual duty: input request, limited/zero-flow-adjusted solve input, and duty from gas states. Energy residual is actual minus adopted. Duty uses kW; flux W/m².

Professional Theory​

Gas-Side Pressure Drop and Mass Conservation​

Let p0,p1p_0,p_1 be absolute pressures in Pa and q0,q1q_0,q_1 actual volume flows in m³/s, positive 0→1. There is no gas inventory; mass is conserved in steady-state and transients. Resistance is quadratic in Kv with near-zero smoothing.

ρ0q0=ρ1q1,p0−p1≈100 ρu(3600Kv)2q0∣q0∣.\rho_0 q_0=\rho_1 q_1, \qquad p_0-p_1\approx 100\,\rho_{\mathrm{u}} \left(\frac{3600}{K_v}\right)^2 q_0|q_0|.

ρ0,ρ1\rho_0,\rho_1 are port densities and ρu\rho_{\mathrm{u}} actual upstream density in kg/m³. The drop formula always uses port-0 q0q_0; reverse flow uses port-1 density. Larger Kv gives smaller drop for fixed flow/state. Kv, area, and coefficient are independent inputs.

External Temperature and Overall Coefficient​

Subscripts u,d\mathrm{u},\mathrm{d} mean actual upstream/downstream. Temperature uses K; m˙=∣ρ0q0∣\dot m=|\rho_0q_0| is kg/s. Composition passes with flow. Specific enthalpy h(p,T,x)h(p,T,x) uses J/kg and incoming composition xx. Actual heat duty in W follows enthalpy difference.

Q˙actual=m˙(hd−hu).\dot Q_{\mathrm{actual}}=\dot m(h_{\mathrm{d}}-h_{\mathrm{u}}).

External fluid is a source/sink at given TextT_{\mathrm{ext}}. Area AA in m² and coefficient UU give UAUA in W/K. Upstream cp,u=(∂h/∂T)p,xc_{p,\mathrm{u}}=(\partial h/\partial T)_{p,x} determines NTU. Let ϕ\phi weight incoming enthalpy:

NTU=UAm˙cp,u,ϕ=e−NTU,hd=ϕhu+(1−ϕ)h(pd,Text,x).\mathrm{NTU}=\frac{UA}{\dot m c_{p,\mathrm{u}}}, \qquad \phi=e^{-\mathrm{NTU}}, \qquad h_{\mathrm{d}} =\phi h_{\mathrm{u}}+(1-\phi)h(p_{\mathrm{d}},T_{\mathrm{ext}},x).

Invert hdh_{\mathrm{d}} at outlet pressure pdp_{\mathrm{d}} for temperature. Higher conductance approaches external temperature. At fixed UAUA and heat capacity, higher mass flow gives lower NTU and smaller enthalpy change per mass.

For negligible pressure drop and constant heat capacity, ϵ=1−e−NTU\epsilon=1-e^{-\mathrm{NTU}} and Td=Text+(Tu−Text)e−NTUT_{\mathrm{d}}=T_{\mathrm{ext}}+(T_{\mathrm{u}}-T_{\mathrm{ext}})e^{-\mathrm{NTU}}. ASHRAE Effectiveness and NTU

Specified Heat Flux​

Flux q ⁣′ ⁣′q\!\prime\!\prime in W/m² times area AA gives requested duty. With flow, heating/cooling limits determine adopted duty. Formulas use W; panel limits use kW.

Q˙req=q′′A,Q˙applied=min⁡ ⁣(Q˙heat,max,max⁡(−Q˙cool,max,Q˙req)),m˙(hd−hu)=Q˙applied.\begin{aligned} \dot Q_{\mathrm{req}} &= q'' A,\\ \dot Q_{\mathrm{applied}} &= \min\!\bigl(\dot Q_{\mathrm{heat,max}}, \max(-\dot Q_{\mathrm{cool,max}},\dot Q_{\mathrm{req}})\bigr),\\ \dot m(h_{\mathrm{d}}-h_{\mathrm{u}}) &= \dot Q_{\mathrm{applied}}. \end{aligned}

Maximum cooling duty is its absolute capacity. Positive duty raises enthalpy, negative lowers it, independent of flow direction. Temperature change also depends on pressures and properties. At equal duty, lower flow gives larger specific enthalpy change.

Zero Heat Transfer and Zero Flow​

With flow, U=0U=0 or zero adopted duty gives hd=huh_{\mathrm{d}}=h_{\mathrm{u}}; pressure drop can still cause throttling temperature change. With zero flow, no cross-port transport occurs and adopted/actual duty are zero. Flux mode retains requested duty and recalculates from current input/limits when flow resumes.

Applicability and Limits​

  • One-sided lumped transfer. External conditions are imposed; use a two-fluid model to solve both streams.
  • No thermal storage. Duty uses current boundary/state; wall and body inertia are outside scope.
  • Global thermal mode. Isothermal mode retains hydraulic resistance; temperature changes and duty require non-isothermal mode.

Common Inspections​

  • Unexpected drop. Check Kv and actual upstream density; convert port-0 flow to m³/s.
  • Unexpected temperature/direction. Identify upstream, then check external temperature, UA, area basis, and flow. Duty follows enthalpy change; check drop for zero-duty temperature differences.
  • Actual differs from request. Compare requested/adopted/actual duty, limits, and zero-flow restriction; check kW versus W/m².
  • Inactive curve/signal. Check non-isothermal mode, curve name/type/coverage, adapter target, signal, and units.