Actuator

An actuator sends a control signal to a selected control target on one device instance. Targets include shut-off valve opening, regulator pressure setpoints, compressor control targets, and heat transfer inputs. The device's control source, movement, and operating constraints determine its response.

Component Appearance and Location​

Expand Signals and Communication in the component library and add Actuator.

Ports and Connections​

Port keyTypeDirectionConnection
signalCONTROLInput (IN)Connect a controller CV, constant signal, or other command source.

Select the target device in the actuator parameters. Keep one output driver per signal node.

Parameters​

Basic Parameters

NamekeyTypeDefault / OptionsDescription
Target Device CategoryTargetComponentClasschoice__UNSELECTED__Target equipment category in the current model.
Target Device LabelTargetComponentIdchoice__UNSELECTED__Select by label and component ID. Copies retain the original target.
Signal OptionSignalKeychoice__UNSELECTED__Select a signal from the target device. Check the selection if the device configuration changes.

Parameter Guidance​

  • Connected device category. Configure the target equipment first, then select a category in the current model that supports actuation.
  • Connected device label. Select the target instance. Use the component ID to distinguish devices with the same label. After copying, check the retained target reference.
  • Signal option. Select an actuation target supported by the device configuration. Check its units, bounds, and control source. For example, constant compressor outlet pressure and constant standard flow use different units. Confirm the signal after switching targets.

The actuator receives a signal. Available targets depend on the device configuration. Use the signal appropriate to the selected physical quantity.

Supported Devices and Targets​

DeviceExample target
Shut-off valveOpening setpoint in percent.
Pressure regulatorOutlet pressure or differential pressure setpoint, depending on regulation mode.
General, centrifugal, and piston compressorsSetpoint or run enable, depending on model, configuration, and control objective.
Heat exchangerExternal medium temperature (°C) or heat flux (W/m²), depending on heat transfer mode and input source.

Example: Configure Heat Exchanger Actuation​

Use a non-isothermal transient. Configure the heat exchanger mode and its signal input before choosing an actuator signal.

Heat exchanger settingSignal optionCommand unit
External Temperature and Overall Coefficient with Temperature Signal as the external medium temperature sourceExternal medium temperature setpoint°C
Specified Heat Flux with Heat Flux Signal as the flux sourceHeat flux setpointW/m²

Heat flux times effective area gives requested heat duty. Convert external commands from kW to W/m² using that area. The results report requested, accepted, and actual heat duty in kW. See Heat exchanger parameters and heat duty.

A model containing only sources, short pipes, and loads has an empty actuator target list. These components support measurement. Configure changes to source or load boundaries in the corresponding component parameters and schedules.

Modeling Steps​

  1. Add a shut-off valve, connect its fluid ports, and set its initial conditions.
  2. Add an actuator and select the shut-off valve category, the valve label, and the opening setpoint.
  3. Connect a constant signal or PID controller output to the actuator input.
  4. Enter the command and controller output limits as percentages, such as 0 to 100. Enable the appropriate signal control source on the valve.
  5. Validate, save, and run a transient. Compare the requested, applied, and actual opening.

For external computation, bind the actuator's signal input in the external-to-platform output channel table of the communication interface. Enable the corresponding signal source on the equipment. See Build a gas network control system.

After changing the target device or quantity, reselect the signal and check the unit. Copying an actuator retains its original target reference.

View Results​

ResultMeaning
Requested valueThe controller or source command.
Applied valueThe target accepted by the device under the active control source and range rules.
Actual valueThe physical state reached by the device, such as opening or speed.

Compare the requested and applied values, then the applied and actual values. A standby signal chain can have a request even when the equipment uses another control source.

Professional Theory​

Actuation Targets and Equipment Response​

The actuator passes engineering values to the equipment model, which processes the setpoint and computes the physical response. A shut-off valve opening request ranges from 0% to 100%. Actual opening follows the configured stroke time. Compressors also follow startup, shutdown, ramp, and operating constraints. See Shut-off valve.

Transient Control Timing​

The steady-state and initial transient physical calculations use each device's own initial or static settings. Control initialization can generate a request at the start. The device responds in subsequent positive-time intervals. To check actuation, compare the transient settings, control source, applied value, and actual value.

Common Checks​

  • Empty device category. Check for equipment that supports actuation. Sources, short pipes, and loads offer measurements.
  • Empty or invalid signal option. Check device configuration, control objective, heat transfer mode, and input source, then select the option again.
  • Request without motion. Check the device control source, transient settings, action time, operating constraints, and protections.
  • Unexpected magnitude or rejected command. Check gauge versus differential pressure, flow basis, and percentage versus fractional opening.
  • Duplicate binding or driver. Use one binding for each actuation target on a device and one output driver per signal node.