Regulator Valve

Reduces downstream pressure or maintains a specified differential for city gates, regulator stations, and offtakes.

Component Appearance and Location​

Expand Pipeline Valve in the component library on the left and find "Regulating Valve".

Created with Fabric.js 5.3.0

Ports and Connections​

Connect port 0 upstream and 1 downstream. Bind external setpoints or measurements using a measurement instrument or actuator.

Parameter List​

Initial Conditions and Regulation Target

NamekeyTypeDefault / OptionsDescription
Initial Operating StateStatuschoiceOpen / ClosedInitial state: Open permits flow/regulation subject to supply/network, Closed blocks. Pre-start plans do not override new initialization; start-time requests apply in first positive interval.
Regulation ModeRegulatorModechoiceOutlet Pressure Control / Differential Pressure ControlOutlet-pressure or minimum-differential control, subject to capacity/constraints/network. After switching, reselect matching actuation signal and check controller units/ranges.
Outlet Pressure Target [MPa(g)]SetPressurereal2Initial outlet gauge target, later changed by schedule/signal. Capacity/constraints can leave actual below target. Converted absolute pressure must be positive.
Pressure Differential Target [MPa]SetDiffreal0.1Minimum differential target; if full-open drop is larger, network and capacity determine actual drop.

Capacity and Operating Constraints

NamekeyTypeDefault / OptionsDescription
Full-Open Capacity ModelCapacityModelchoiceExpansion/Choked Flow / Outlet-Density Pressure Difference / Pressure-Squared DifferenceChoose equipment capacity model. Expansion uses full-open xT and ideal-gas ratio. Outlet-density uses outlet density/drop. Pressure-squared uses inlet temperature and effective mean-pressure Z, choking at absolute ratio ≤0.5.
Full-Open Kv [m³/(h·bar⁰·⁵)]FullOpenKVreal5000Positive full-open Kv from equipment data.
Full-Open Critical Ratio xTFullOpenXTreal0.5Required expansion-model full-open xT in (0,1] from vendor.
Enable Upstream Pressure MaintenanceEnableMinInletPressurecheckOffLimits flow to maintain minimum upstream pressure; disabled retains standby value.
Minimum Upstream Pressure [MPa(g)]MinInletPressuretext—Required with upstream maintenance; converted absolute pressure must be positive.
Enable Maximum Mass FlowEnableMaxMassFlowcheckOffLimits forward mass flow; disabled retains standby value.
Maximum Mass Flow [kg/s]MaxMassFlowtext—Positive forward mass-flow upper limit, required when enabled.

Control Mode

NamekeyTypeDefault / OptionsDescription
Control SourceControlModechoice0Plans change state/target; signals use matching adapter setpoints with initial state. Steady-state uses initial conditions, retaining standby plans/wiring.
Setpoint Transition Time [s]SetpointRampTimereal0Plan-only linear ramp from activation/current target. Zero immediate; new targets restart from reached value. Ramps continue while closed and may exceed remaining simulation duration.
Regulation ScheduleOutletPressurePlantableConfigure one row at a timeTargets activate at row time and follow transition duration. Pre-start plans do not override initialization; start-time requests apply in first positive interval. Targets continue while closed. Modes save separate schedules.
Regulation Schedule / Effective TimeOutletPressurePlan.timedatetime2026-01-01 00:00:00When this target begins, not when reached.
Regulation Schedule / Operating StateOutletPressurePlan.statuschoiceOpen / ClosedOpen/close at activation; start-time requests apply in first positive interval. Setpoint ramp is not valve stroke time.
Regulation Schedule / Target Outlet Pressure [MPa(g)]OutletPressurePlan.setPressurereal2Outlet target, required even while closed as schedules continue. Absolute pressure must be positive.
Regulation SchedulePressureDiffPlantableConfigure one row at a timeTargets activate at row time and follow transition duration. Pre-start plans do not override initialization; start-time requests apply in first positive interval. Targets continue while closed. Modes save separate schedules.
Regulation Schedule / Effective TimePressureDiffPlan.timedatetime2026-01-01 00:00:00When this target begins, not when reached.
Regulation Schedule / Operating StatePressureDiffPlan.statuschoiceOpen / ClosedOpen/close at activation; start-time requests apply in first positive interval. Setpoint ramp is not valve stroke time.
Regulation Schedule / Target Differential [MPa]PressureDiffPlan.setDiffreal0.1Inlet-minus-outlet differential target, required even while closed as schedules continue.

Parameter Guidance​

  • Regulation mode. Outlet Pressure Control uses MPa(g); Differential Pressure Control uses MPa.
  • Full-open capacity. Select a model and full-open Kv from equipment data. Expansion/choked flow also needs full-open xT, 0 < xT ≤ 1. Capacity Models
  • Constraints. Independently enable upstream pressure maintenance in MPa(g) and maximum mass flow in kg/s.
  • Transient control. Plan rows specify effective time, state, and target for the active mode. Transition time ramps pressure and differential pressure targets, and states switch at event times. To use signal control, bind an actuator to the valve and choose Outlet pressure setpoint or Differential pressure setpoint in Signal Option, according to the active mode. Steady-state uses panel values.

Modeling Steps​

  1. Connect and check direction.
  2. Set initial state, target, and equipment-compatible capacity model.
  3. Enable pressure/flow constraints as needed and set transient plans or signals.
  4. Check pressures, flow, active constraints, and target reachability.

View Results​

  • Compare actual outlet pressure or differential to its target.
  • For deviations, inspect pressures, mass flow, and active capacity, upstream-pressure, or flow constraints. Check model and Kv, then xT for expansion/choked flow.
  • Transient setpoint curves show the active target and any planned ramp.

Professional Theory​

Regulation Targets and Constraints​

Let pinp_{\mathrm{in}}, poutp_{\mathrm{out}} be absolute pressures, m˙\dot m forward mass flow, and m˙full\dot m_{\mathrm{full}} current full-open capacity. Calculations use Pa and kg/s. Gauge setpoint and minimum upstream pressure add the global reference; differential needs unit conversion only.

Open forward flow must satisfy target, full-open capacity, and enabled constraints. Equality means the corresponding target or limit is reached.

ConditionForward-flow constraint
Outlet pressurepout≤psetp_{\mathrm{out}}\le p_{\mathrm{set}}
Differentialpin−pout≥Δpsetp_{\mathrm{in}}-p_{\mathrm{out}}\ge\Delta p_{\mathrm{set}}
Full-open capacitym˙≤m˙full\dot m\le\dot m_{\mathrm{full}}
Upstream pressure, if enabledpin≥pminp_{\mathrm{in}}\ge p_{\mathrm{min}}
Maximum mass flow, if enabledm˙≤m˙max\dot m\le\dot m_{\mathrm{max}}

The target is reached when it governs. If capacity governs, flow reaches full-open capacity while the network determines pressures. Pressure-maintenance or flow limits can instead set the operating point. Closing, reverse pressure, or infeasible forward constraints gives zero flow.

Full-Open Capacity Models​

Full-open capacity is the maximum mass flow at current conditions, calculated from full-open Kv and gas state.

  • Expansion/choked flow. Uses full-open Kv and fixed xT with the Shut-off Valve Expansion Model.
  • Outlet-density differential. Uses Kv, outlet density, and differential. Model
  • Pressure-squared difference. Uses inlet temperature and effective mean pressure, unlike the shut-off model using actual upstream state. Comparison

For pressure-squared capacity, use pe=max⁡(pout,pin/2)p_e=\max(p_{\mathrm{out}},p_{\mathrm{in}}/2) and pm=(pin+pe)/2p_m=(p_{\mathrm{in}}+p_e)/2. Evaluate density ρm\rho_m with inlet gas and temperature at pmp_m. For forward flow away from zero differential,

m˙full=Kv,full36000ρm(pin2−pe2)2pm.\dot m_{\mathrm{full}}= \frac{K_{v,\mathrm{full}}}{36000} \sqrt{\frac{\rho_m\left(p_{\mathrm{in}}^2-p_e^2\right)}{2p_m}}.

Once outlet pressure falls to half inlet pressure, effective outlet pressure holds at pin/2p_{\mathrm{in}}/2. At fixed inlet state, further outlet reduction leaves capacity at its critical value.

Mass Conservation and Throttling Temperature​

Forward flow conserves mass and passes composition. Non-isothermal temperature uses the outlet Joule–Thomson coefficient and a first-order isenthalpic approximation. Throttling

Applicability and Limits​

  • Models forward single-phase gas throttling. Supply needs higher inlet pressure and depends on both boundaries.
  • Capacity varies with conditions; reachability also depends on pressure/flow constraints.
  • Transient transition time models target changes, not stem or actuator dynamics.

Common Inspections​

  • Target mismatch. Check mode and units: MPa(g) for outlet/minimum upstream pressure, MPa for differential. Check supply and downstream boundaries.
  • Open with zero flow. Check direction, forward pressure, downstream pressure versus target, differential, and minimum upstream pressure.
  • Low flow. Check active constraints, capacity model, Kv, and xT if relevant. Compare mass-flow limits in kg/s.
  • Unexpected transient target. Check source, plan state/timing/ramp, or adapter target, signal, and units. Inspect the active setpoint curve.