Single-Port Relief Valve
Opens and closes automatically with inlet pressure and discharges gas to a specified backpressure.
Component Appearance and Location
Find Single-Port Relief Valve under Pipes and Valves.
Ports and Connections
Connect port 0 to the protected node and set Discharge Backpressure in MPa(g). Enter zero when discharge absolute pressure equals the global gauge reference. Use a Two-Port Relief Valve for a solved discharge header.
Parameter List
Equipment Specifications
| Name | key | Type | Default / Options | Description |
|---|---|---|---|---|
| Discharge Flow Model | HydraulicModel | choice | Equivalent Nozzle / Pressure-Squared Difference / Approximate Orifice | Equivalent nozzle approximates Saint-Venant–Wantzel isentropic flow; pressure-squared uses absolute-pressure squares and mean-state Z; approximate orifice uses empirical expansion and inlet heat capacity. Shared Kv/characteristics, all subcritical/critical. Reinitialize/check after switching. |
| Characteristic Type | ValveCurveType | choice | Linear / Equal-Percentage / Parabolic / Custom | Opening–Kv relation. Two-state uses only full-open point/custom 100% endpoint; curve action uses actual opening. |
| Full-Open Kv [m³/(h·bar⁰ᐧ⁵)] | FullOpenKV | real | 5000 | Positive Kv at 100% from equipment data; shared across discharge models, which determine flow. |
| Zero-Opening Kv [m³/(h·bar⁰ᐧ⁵)] | FullCloseKV | real | 0 | Zero-opening characteristic endpoint affects partial-opening capacity. No greater than open Kv. Fully closed flow is zero; this is not leakage. |
| Valve Kv Curve | CurveLibraryValveKvName | choice | __UNSELECTED__ | Opening–Kv curve covering 0%/100%, linearly interpolated. Two-state uses last point; curve action actual opening. Standby open/zero Kv unused. |
| Discharge Backpressure [MPa(g)] | BackPressure | real | 0 | Fixed discharge gauge backpressure; zero for the global gauge reference environment. Forward relief needs inlet above backpressure and an open valve. |
Operating Constraints
| Name | key | Type | Default / Options | Description |
|---|---|---|---|---|
| Pressure Action Model | ActionModel | choice | Two-State Pop Action / Independent Opening/Closing Curves | Two-state switches fully open/closed and holds within hysteresis. Independent curves move with opening/closing times and hold within the band; reversals continue from current opening. |
| Opening Pressure [MPa(g)] | MaxOnPressure | real | 10 | Opening triggers at/above inlet threshold: immediate for two-state, timed curve otherwise. Does not clamp inlet pressure; backpressure affects capacity, not threshold. |
| Closing Pressure [MPa(g)] | MaxOffPressure | real | 8 | Closing triggers at/below threshold, strictly below opening. Two-state immediate, curve timed; hysteresis holds state/opening. |
| Initial Actual Opening [%] | InitialOpening | real | 0 | Curve-action initial opening. Transient first frame uses it, action starts at first positive step. Steady hysteresis retains it; outside uses thresholds. Continuation restores opening/progress. |
| Opening Full-Stroke Time [s] | OpenTime | real | 5 | 0→100% opening duration. Zero immediate; partial travel continues at current curve position for remaining time. |
| Opening Action Curve | CurveLibraryOpeningMotionName | choice | __UNSELECTED__ | Opening action from (0,0) to (100,100), both columns strictly increasing; 2–100 points, linear interpolation, continuation from current opening. |
| Closing Full-Stroke Time [s] | CloseTime | real | 5 | 100→0% closing duration. Zero immediate; partial travel uses remaining curve time. |
| Closing Action Curve | CurveLibraryClosingMotionName | choice | __UNSELECTED__ | Closing action from (0,100) to (100,0); time strictly increasing, opening strictly decreasing; 2–100 points, linear interpolation from current opening. |
Parameter Guidance
- Discharge model. Choose equivalent nozzle, pressure-squared difference, or approximate orifice according to equipment data. Built-in characteristics use full-open Kv, with zero-opening Kv also required for independent opening and closing curves. For a custom characteristic, enter or reference an opening–Kv curve that covers 0% and 100%. Discharge flow models
- Thresholds. Opening and closing pressures use MPa(g), with closing strictly below opening.
- Action. Choose two-state pop action or independent curves. Curves require initial opening and separate transient opening/closing stroke times; each positive-time direction needs its action curve. Action
Enter Characteristic and Action Curves
Choose Edit Local Curve or Reference Curve Database separately for the valve flow coefficient, opening action, and closing action curves. Enter local points or select a named curve of the same type.
| Curve | Horizontal axis | Vertical axis and requirements |
|---|---|---|
| Custom Kv | Opening percentage, strictly increasing and covering 0% to 100% | Absolute Kv, nonnegative and nondecreasing, with a positive full-open value. |
| Opening action | Full-stroke time percentage, strictly increasing and covering 0% to 100% | Actual opening percentage, strictly increasing from 0% to 100%. |
| Closing action | Full-stroke time percentage, strictly increasing and covering 0% to 100% | Actual opening percentage, strictly decreasing from 100% to 0%. |
Set the duration separately using the full-stroke time for each direction. Action curves apply during transients with independent opening and closing curves and a positive stroke time for that direction. A stroke time of zero takes the valve to the endpoint immediately. Choose a curve source.
Modeling Steps
- Connect the protected side and set backpressure.
- Enter capacity, Kv, thresholds, and action data.
- Cover pressurization, relief, and reseating in transient timing; check curves and steps.
- Inspect inlet pressure, opening, discharge, and backpressure.
View Results
- Compare pressure, action state, and actual opening for opening, closing, or hold.
- Compare relief state, effective Kv, backpressure, and flow for normal discharge, blocking, or unavailable capacity. Standard discharge uses global standard conditions.
Professional Theory
Thresholds and Actual Opening
Inlet gauge pressure triggers opening and reseating. Hysteresis between thresholds reduces cycling. Backpressure affects flow; action thresholds compare inlet pressure with settings.
| Inlet pressure | Two-state action | Independent curves in transients |
|---|---|---|
| At/above opening | Fully open | Advance on opening curve |
| At/below closing | Fully closed | Advance on closing curve |
| Between | Hold state | Pause and hold opening |
Action curves use full-stroke time percentage horizontally and actual opening percentage vertically. Opening runs 0→100%, closing 100→0%. Retriggering or reversing continues from the current opening on the corresponding curve. Zero stroke time reaches the endpoint immediately on triggering. Curve Database
For independent curves, steady-state determines opening from solved inlet pressure, using initial actual opening within hysteresis. The transient initial frame uses initial opening; action advances from the first positive step. Continuation restores saved opening and progress.
Discharge Flow Models
Let and be inlet/backpressure absolute pressures in Pa and discharge in kg/s. Two-state full opening uses full-open Kv or the custom 100% endpoint. Independent curves use actual opening and zero-opening Kv as a characteristic endpoint. Flow is zero if fully closed, effective Kv is zero, or . Effective Kv
For permitted discharge, . Flow is subcritical for and critical for . With fixed inlet state and effective Kv, lowering backpressure in the critical regime does not increase flow.
Equivalent Nozzle
Use the inlet ideal-gas heat capacity ratio for the critical ratio. With inlet density in kg/m³ and equivalent area in m²,
Pressure-Squared Difference
Use regulator effective mean pressure: , , with inlet gas and temperature. Substitute , , and effective Kv into the regulator capacity formula. Critical ratio is 0.5. Formula
Approximate Orifice
Estimate from inlet temperature and mean molar mass. Clamp temperature to 510–710 °R and molar mass to 15–100 kg/kmol. The correlation is
Replace by in the nozzle critical-ratio formula and set . Evaluate throat density at and in K. Estimate velocity with inlet ideal-gas heat capacity in J/(kg·K), giving
Applicability and Limits
- Covers single-phase gas at fixed backpressure. Use a Two-Port Valve for header accumulation, losses, or shared headers.
- Opening pressure triggers action; protected pressure still depends on supply, network, and capacity. Check rated capacity and selection against equipment data and standards.
- Temperature/composition results describe the inlet. Orifice temperature is for capacity; model the discharge network to inspect its temperature.
Common Inspections
- Open with no flow. Compare inlet/backpressure, then opening and Kv.
- Pressure still rises. Check full stroke, supply, capacity, and backpressure; assess critical discharge with inlet state and Kv.
- Delayed reseating. Check closing threshold and backpressure; high backpressure may prevent reaching reseat pressure. Check closing time and opening for curve action.
- Unexpected opening. Check model, initial opening, hysteresis, curve direction/reference/timing, and saved continuation state.