Two-Port Relief Valve

Opens and closes automatically with inlet pressure and discharges gas into an explicitly modeled downstream network.

Component Appearance and Location​

Find Two-Port Relief Valve under Pipes and Valves in the left library.

Created with Fabric.js 5.3.0

Ports and Connections​

Port keyTypeNameConnection
0FLUIDFluid inletProtected network or equipment
1FLUIDDischarge outletRelief header or downstream boundary

Backpressure is the solved discharge outlet pressure. Connect the outlet to the network to include header losses or shared headers. Use the Single-Port Relief Valve for fixed discharge environment pressure.

Parameter List​

Equipment Specifications

NamekeyTypeDefault / OptionsDescription
Discharge Flow ModelHydraulicModelchoiceEquivalent Nozzle / Pressure-Squared Difference / Approximate OrificeEquivalent nozzle approximates Saint-Venant–Wantzel isentropic flow; pressure-squared uses absolute-pressure squares and mean-state Z; approximate orifice uses empirical expansion and inlet heat capacity. Shared Kv/characteristics, all subcritical/critical. Reinitialize/check after switching.
Characteristic TypeValveCurveTypechoiceLinear / Equal-Percentage / Parabolic / CustomOpening–Kv relation. Two-state uses only full-open point/custom 100% endpoint; curve action uses actual opening.
Full-Open Kv [m³/(h·bar⁰ᐧ⁵)]FullOpenKVreal5000Positive Kv at 100% from equipment data; shared across discharge models, which determine flow.
Zero-Opening Kv [m³/(h·bar⁰ᐧ⁵)]FullCloseKVreal0Zero-opening characteristic endpoint affects partial-opening capacity. No greater than open Kv. Fully closed flow is zero; this is not leakage.
Valve Kv CurveCurveLibraryValveKvNamechoice__UNSELECTED__Opening–Kv curve covering 0%/100%, linearly interpolated. Two-state uses last point; curve action actual opening. Standby open/zero Kv unused.

Operating Constraints

NamekeyTypeDefault / OptionsDescription
Pressure Action ModelActionModelchoiceTwo-State Pop Action / Independent Opening/Closing CurvesTwo-state switches fully open/closed and holds within hysteresis. Independent curves move with opening/closing times and hold within the band; reversals continue from current opening.
Opening Pressure [MPa(g)]MaxOnPressurereal10Opening triggers at/above inlet threshold: immediate for two-state, timed curve otherwise. Does not clamp inlet pressure; backpressure affects capacity, not threshold.
Closing Pressure [MPa(g)]MaxOffPressurereal8Closing triggers at/below threshold, strictly below opening. Two-state immediate, curve timed; hysteresis holds state/opening.
Initial Actual Opening [%]InitialOpeningreal0Curve-action initial opening. Transient first frame uses it, action starts at first positive step. Steady hysteresis retains it; outside uses thresholds. Continuation restores opening/progress.
Opening Full-Stroke Time [s]OpenTimereal50→100% opening duration. Zero immediate; partial travel continues at current curve position for remaining time.
Opening Action CurveCurveLibraryOpeningMotionNamechoice__UNSELECTED__Opening action from (0,0) to (100,100), both columns strictly increasing; 2–100 points, linear interpolation, continuation from current opening.
Closing Full-Stroke Time [s]CloseTimereal5100→0% closing duration. Zero immediate; partial travel uses remaining curve time.
Closing Action CurveCurveLibraryClosingMotionNamechoice__UNSELECTED__Closing action from (0,100) to (100,0); time strictly increasing, opening strictly decreasing; 2–100 points, linear interpolation from current opening.

Parameter Guidance​

  • Discharge model. Select equivalent nozzle, pressure-squared difference, or approximate orifice according to equipment data. Enter Kv for a built-in characteristic or enter or reference an opening–Kv curve for a custom characteristic. The capacity formulas and effective Kv rules match the single-port relief valve.
  • Opening/closing pressures. Both use inlet MPa(g); closing must be strictly below opening.
  • Pressure action. Choose two-state pop action or independent opening/closing curves. Curve action needs initial actual opening, separate transient stroke times, and a corresponding action curve for each positive-time direction. Action and Continuation

Enter Characteristic and Action Curves​

Set separate curve sources for custom Kv, opening action, and closing action. Enter points on this valve or select a named curve of the same type. Enter absolute Kv against opening percentage and actual opening percentage against full-stroke time percentage for action curves. See the single-port relief valve curve requirements for endpoints, monotonicity, and zero stroke time. Choose a curve source.

Modeling Steps​

  1. Connect inlet to protection and outlet to relief header. For known terminal discharge pressure, use a load pressure boundary at the header end. Load Boundaries
  2. Set capacity, Kv, pressures, and action data; reinitialize and check after model changes.
  3. Cover pressurization, relief, and reseating in transient time settings; check curves and steps.
  4. Inspect pressures, flows, actual opening, backpressure, and relief state.

View Results​

  • Compare inlet with opening and closing pressures, state, and actual opening.
  • Treat outlet pressure as actual backpressure; distinguish blocked, subcritical, and critical discharge using inlet pressure and effective Kv.
  • Compare flows on the same units and state basis; non-isothermal results also show throttling temperature changes.

Professional Theory​

Downstream Backpressure and Discharge​

For absolute inlet/outlet pressures pinp_{\mathrm{in}}, poutp_{\mathrm{out}} in Pa, use pb=poutp_b=p_{\mathrm{out}} and r=pout/pinr=p_{\mathrm{out}}/p_{\mathrm{in}} for capacity. Inlet pressure still triggers action. Both flows are zero if closed, effective Kv is zero, or pin≤poutp_{\mathrm{in}}\le p_{\mathrm{out}}. Capacity and Critical Ratio

Header terminal pressure is a boundary; valve outlet backpressure also depends on header resistance and flow. Shared-header valve changes can alter other valves. For fixed inlet state and Kv, rising backpressure beyond the critical ratio makes discharge subcritical and flow dependent on backpressure again.

Mass Conservation and Outlet Temperature​

Forward discharge transports incoming composition and conserves inlet/outlet mass flow:

m˙=ρinqin=ρoutqout.\dot m=\rho_{\mathrm{in}}q_{\mathrm{in}}=\rho_{\mathrm{out}}q_{\mathrm{out}}.

Here ρ\rho is local density in kg/m³ and qq local actual volume flow in m³/s. Different densities can give different actual volume flows.

Non-isothermal outlet temperature follows isenthalpic throttling. Given inlet temperature TinT_{\mathrm{in}}, pressures, and composition x\boldsymbol{x}, solve

h(pout,Tout,x)=h(pin,Tin,x).h(p_{\mathrm{out}},T_{\mathrm{out}},\boldsymbol{x}) =h(p_{\mathrm{in}},T_{\mathrm{in}},\boldsymbol{x}).

Here hh is specific enthalpy in J/kg and TT uses K. Outlet constant-pressure heat capacity iteratively corrects ToutT_{\mathrm{out}} to satisfy equal enthalpy. Approximate-orifice temperature is used for capacity; discharge outlet temperature follows this throttling relation.

Applicability and Limits​

  • Models single-phase gas discharge into a modeled downstream network; solve discharge pressure, flow, and temperature with the header and terminal boundary.
  • Opening pressure triggers action; protected pressure still depends on supply, capacity, and backpressure. Check rated capacity and equipment selection against equipment data and applicable standards.

Common Inspections​

  • Open but no flow. Compare pressures, opening, and Kv. If backpressure reaches inlet pressure, check terminal boundaries and other discharges.
  • Lower per-valve flow with multiple valves. Compare backpressure and relief states; check shared-header diameter, resistance, and boundaries.
  • Pressure rises or reseating is delayed. Compare relief and supply, opening, and whether inlet can reach closing pressure. Action Checks
  • Different volume flows. Check actual versus standard basis. Compare mass flow or each local volume flow times density.