City Gas Gate Station Pressure Regulating Gas Supply
A simplified single-path city gate supplies gas through a trunk, regulator, and downstream branch to a terminal. Steady-state isothermal analysis checks outlet target, pressure-drop allocation, and flow at given boundary pressures.
Study Overview
| Item | Configuration |
|---|---|
| Scenario | Single-path city gate regulation |
| Network | 1 source, 2 pipes, 1 regulator, 1 load |
| Analysis | Steady-state, isothermal |
| Boundaries | Upstream 0.4 MPag; downstream 0.02 MPag |
| Control | Outlet pressure 0.04 MPag |
| Results | Supply, regulator pressures/drop, pipe losses, continuity |
| Scope | Pressure matching and steady-state supply capacity |
| Status | success / 100% |
Working Conditions Background and Pipe Network Structure
Working Condition Background
Incoming pressure is 0.4 MPag, regulator target 0.04 MPag, and terminal 0.02 MPag. The downstream branch still needs pressure difference to overcome friction.
Pipe Network Structure

City Gate Source → Urban Trunk → Regulator → Downstream Distribution Branch → Terminal.
The image labels Low-Pressure Branch and Residential Load identify the downstream branch and terminal.
One valve represents regulation; filtering, metering, heating, standby trains, shutdown, and venting are omitted. This suits normal-operation hydraulics and pressure control.
Pipeline and Equipment Parameters
| Pipe | Length | Diameter | Wall | Roughness | Friction |
|---|---|---|---|---|---|
| Urban trunk | 2000 m | 300 mm | 8 mm | 0.045 mm | Colebrook |
| Distribution branch | 500 m | 150 mm | 5 mm | 0.045 mm | Colebrook |
The entrance and exit elevations of the two sections of pipeline are both 0 m. This example does not consider the impact of terrain height difference on pressure distribution.
Boundary Conditions and Simulation Setup
Air Source and Load Boundaries
| Boundary | Label | Setting |
|---|---|---|
| Source | City Gate Source | 0.4 MPag pressure |
| Load | Residential Load | 0.02 MPag terminal pressure |
Both ends impose pressure; boundaries, pipes, and regulation jointly determine steady flow.
Regulator Settings
| Setting | Value |
|---|---|
| State | Open |
| Mode | Outlet pressure |
| Target | 0.04 MPag |
The 20 kPa target-to-terminal difference is the downstream branch drop when regulation reaches target.
Simulation Settings
| Setting | Value |
|---|---|
| Simulation / thermal | Steady-state / isothermal |
| Temperature | 15 °C |
| EOS | BWRS |
| Gas | NaturalGas |
| Gauge reference | 101.325 kPa(a) |
| Standard state | 101.325 kPa(a), 20 °C |
NaturalGas mole percentages: methane 90%, ethane 5%, propane 2%, nitrogen 2%, carbon dioxide 1%.
Steady State Calculation Results and Analysis
| Section | Inlet MPag | Outlet MPag | Drop kPa | Standard Nm³/h |
|---|---|---|---|---|
| Trunk | 0.40000 | 0.39934 | 0.66 | 2277.17 |
| Regulator | 0.39934 | 0.04000 | 359.34 | 2277.17 |
| Distribution branch | 0.04000 | 0.02000 | 20.00 | 2277.17 |
Outlet reaches 0.04000 MPag. Drops total 380.00 kPa, matching boundaries; the regulator takes 94.6%.
Mass flow is equal across the regulator; standard flow is 2277.17 Nm³/h at both ends. Isothermal depressurization reduces density, increasing actual flow from 448.58 to 1603.04 m³/h.

The steady result instant is 2026-01-01 00:00:00. Data blocks use interface precision; use the table for drop.
Simulation Capabilities Reflected in Calculation Examples
| Capability | Application |
|---|---|
| Pressure-boundary solving | Supply flow from source/terminal pressures |
| Regulation | Drop required for 0.04 MPag outlet |
| Coupling | Trunk, valve, and branch pressures/flow |
| Loss allocation | Separate pipe and valve drops |
| Continuity | Series standard flow and node conservation |
| Target check | Actual versus set outlet pressure |
Results Viewing Process
- Open City Gate Pressure Regulation in Simulation Marketplace, start, and wait.
- Select the completed job; inspect steady residuals under Other Results.
- Create a regulator data block and check pressures, setpoint, and flows.
- Check both pipe pressures/drops and standard flow against the table.
The result viewing process only describes the result entry that needs to be checked in this case. For general job switching, trend chart and data block operation methods on the Workbench, see "Running calculations and viewing results" in the quick start.
Extended Comparison Conditions
| Comparison | Change | Compare | Purpose |
|---|---|---|---|
| Target | Outlet setpoint | Valve/pipe drops and flow | Supply effect |
| Lower supply | Source pressure | Inlet, regulation, flow | Regulation margin |
| Peak load | Terminal flow boundary | Terminal/minimum pressure, state | Peak capacity |
| Branch modification | Diameter or length | Drop, pressure, flow | Upgrade comparison |
| Capacity limit | Equipment capacity model/data | Active constraint, outlet, flow | Target reachability |
| Parallel regulation | Add parallel train | Split, pressure, load | Coordination |
When carrying out extended working condition comparison, only change a single parameter to be compared each time, and keep other boundary conditions and equipment parameters consistent. For load changes over time, switching of pressure regulating equipment or upstream pressure disturbances, transient operating conditions should be established based on this steady-state model, and corresponding time-varying boundaries or control conditions should be set.